Permit Number: T21CM02888
Parcel: 12213190B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM02888
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/11/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM02888

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Denied
1. The Shear Walls are shown in the North South direction on Drawing A1. Verify how building will resist Lateral Loads in East West direction. Submit response.

BUILDING REVIEW COMMENTS:
Approved

ELECTRICAL REVIEW COMMENTS
Approved

MECHANICAL REVIEW COMMENTS:
Approved

PLUMBING REVIEW COMMENTS:
Denied
Hydromechanical grease interceptors. Hydromechanical grease interceptors (HGI), which are generally installed inside, may be used when there are four (4) or fewer fixtures. The minimum size HGI to be installed shall be rated no smaller than 25 gallon per minute with a 50 pound grease capacity. Flow Control devices shall be designed and installed so that the total flow through such devices shall at no time be greater than the rated flow. See sheet P3 (note P-6). Demonstrate compliance.
06/15/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM02888
1526 N Alvernon Way
Food Service

TRANSMITTAL: June 15, 2021
This site is located in the C-1 zone (UDC 4.7.20). Construction Services is a permitted use in this zone (Table 4.8-4) subject to Use Specific Standards 4.9.4.M.1 & 5 and 4.9.13.O.

1. Zoning has reviewed the building plans for compliance with DP21-0026 and the proposed plans appear to match what is shown on the DP. Until the DP is approved and the plans match Zoning cannot approve the building plans.

If you have any questions about this transmittal, please contact Elisa Hamblin or Elisa.Hamblin@tucsonaz.gov.