Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T21CM02724
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/26/2021 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Passed | |
| 03/30/2021 | JVINCEN1 | FIRE | REVIEW | Approved | |
| 04/15/2021 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 04/15/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. General: In the report provided by PZSE,Inc. Structural Engineers for the UNIRAC RM Roof Mounted Ballasted Photovoltaic Panel Support System, the structural engineer's seal is not dated and indicates the license expired on 12-31-20. Please update. |
| 04/21/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. Provide a grounding detail for the racking and module grounding. NEC 690.43. Please update the plans and re-submit. Ref; 2018 IBC sec 107.2.1, 2017 NEC, City of Tucson Commercial Permit/Plan Submittal Requirements. |
| 05/26/2021 | SAMUEL ROGERS | ZONING | REVIEW | Reqs Change | FROM: Samuel Rogers PDSD Zoning Review Section PROJECT: T21CM02724 Roof Top Solar- Commercial (1st Review) 6046 E 30th St. TRANSMITTAL DATE: 05/26/2021 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 01. COMMENT: A portion of the structure on the west side of the property does not appear to be permitted. All structures that are proposed to have solar installed on them must be permitted. Either get a for permit the structure or provide evidence that the structure was permitted. If you have any questions about this transmittal, Contact Samuel Rogers at Samuel.Rogers@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/26/2021 | NGARCIA3 | OUT TO CUSTOMER | Completed |