Permit Number: T21CM02677
Parcel: 11504479D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM02677
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/05/2021 JVINCEN1 FIRE REVIEW Approved
04/08/2021 ROBERT SHERRY WATER REVIEW Completed
04/21/2021 SSHIELD1 ENGINEERING REVIEW Passed
04/21/2021 STEVE SHIELDS ZONING REVIEW Approved
04/22/2021 LBOWERS1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Reqs Change
04/22/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM02677

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
NA

BUILDING REVIEW COMMENTS:
Denied
1. The allowable square footage on the cover page is incorrect.
2. Please provide an explanation of the occupant load calculation for the bar area and the lobby. The occupant load factors
used for these areas are not appropriate and not in compliance with Table 1004.5. Please provide clarification for the
decisions made.
3. The accessible route and forward approach clearances are not maintained to the restroom. There is equipment that
reduces these clearances.
4. The exit access path minimum width is not maintain upon exiting the restroom.
5. As the construction is IA construction, provide confirmation that the column located in the bar area meets the requirements
of Table 601. This is column is required to have a 3 hour fire resistance rating.
6. No demolition plan provided.
ELECTRICAL REVIEW COMMENTS
Approved

MECHANICAL REVIEW COMMENTS:
Denied
1. There is a Type II hood indicated on the plans. Provide all details and manufacture specifications.

PLUMBING REVIEW COMMENTS:
Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/23/2021 IMONSHI1 OUT TO CUSTOMER Completed