Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T21CM02471
Parcel: 134130580

Review Status: Completed

Review Details: OTHER

Permit Number - T21CM02471
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/15/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.

Indicate conductor sizes, quantities and types for the secondary feeders to the new electrical service from the Utility Transformer.

Please update the plans and re-submit.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, City of Tucson Commercial Permit/Plan Submittal Requirements.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/16/2021 IMONSHI1 OUT TO CUSTOMER Completed