Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T21CM02412
Parcel: 117100370

Address:
101 W 6TH ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM02412
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/29/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/04/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The maximum distance of the public lavatory from the hot water source (i.e. the recirculating hot water loop) is 6” for a ¾” branch pipe and 24” for a ½” branch pipe, not 22-feet. Reference: Section 404.5, IECC 2018. [Initial comment: Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.]
2. Provide drawings sealed by an Arizona Registrant.
08/12/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following Electrical plan review comments. Also provide a written response.

Justify 16w per sq-ft allowed per 2018 IEC for the lighting.. Could not find this in the book.

Verify that the lamp color temperature output does not exceed 3500K for the exterior luminaires OLC section 402.1.

The load calculations for the unit heaters shown in the panel schedule do not correlate with the unit heater specs on the mechanical plan for KW and OCPD size. Revise the electrical load calculations on the electrical plan.

Ref; 2018 IBC 107.2.1, 2017 NEC. City of Tucson Commercial Plan/Permit Submittal Requirements. 2012 Tucson/Pima County Outdoor Lighting Code (OLC).