Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T21CM02412
Parcel: 117100370

Address:
101 W 6TH ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM02412
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/20/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
05/20/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Comment not addressed. [Initial comment: Provide the size and serial number of the water meter serving this building, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2018.]
06/07/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Stair Beam Design Structural Calculations: These calculations must be sealed, signed, and dated by the engineer of record. Please provide.
2. Stair Retaining Wall Structural Calculations: These calculations must be sealed, signed, and dated by the engineer of record. Please provide.
3. Previous Comment 11; Sheet A2.1; Keynote 3: Please provide Detail 8/A2.1 for the Wall Types.
4. Previous Comment 15; Structural Notes: No structural notes for material specifications were provided in this submittal. Please provide.
5. Previous Comment 16; Special Inspections Certificate: No Special Inspections Certificate was provided in this submittal. Please provide.
6. General: Please provide written responses to all review comments.
06/16/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.

Provide compliance with the 2018 IECC for the lighting.

Provide full compliance with the 2012 Tucson/Pima County Outdoor Lighting Code for the exterior luminaires.

The assigned lighting branch circuits do not correlate with the panel schedule.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2012 Tucson/Pima County Outdoor Lighting Code (OLC),

City of Tucson Commercial Plan Submittal Requirements