Permit Number: T21CM02091
Parcel: 11515214B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM02091
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/10/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
05/10/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
05/25/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/07/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.

Per the previous electrical plan review, the following exterior lighting information was requested in order to verify compliance with the 2012 Tucson/Pima County Outdoor Lighting Code. Please address the following in detail as requested.

#1. Provide plans and evidence on the plans that the proposed exterior lighting fully complies with the Outdoor Lighting Code. See section 104 for plan submittal requirements.



Item # 1a, Shielding for each type of luminaire (per manufacturer) Full Cut-Off or Un-Shielded.

Item #1b Total lumen calculations ,#1 c lighting area and option used from Table 401.1, Total lumen cap or Lumens allowed per Table 401.1 vs Total proposed Lumens.

Item # 1c, Show all new as well as existing exterior luminaires in a lighting site plan. All exterior luminaires for this parcel must be included in the total lumen calculations.

Item #1e Provide total luminaire quantity.

Item # f. Special Inspection note.

Please address Items # 1g and h.



Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2012 Tucson/Pima County Outdoor Lighting Code,

City of Tucson Commercial Plan Submittal Requirements