Review Date Reviewer's Name Type of Review Description Status Comments
04/06/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide locking access port caps for the new condensing units per Section 1101.10, IMC 2018 or locate the condensing units in a controlled space.
04/07/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/08/2021 PCAMARE1 OUT TO CUSTOMER Completed