Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM02054
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/10/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 05/10/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 05/25/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/03/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. Per the previous electrical plan review, the following exterior lighting information was requested in order to verify compliance with the 2012 Tucson/Pima County Outdoor Lighting Code. Please address the following in detail as requested. #1. Provide plans and evidence on the plans that the proposed exterior lighting fully complies with the Outdoor Lighting Code. See section 104 for plan submittal requirements. Item # 1a, Shielding for each type of luminaire (per manufacturer) Full Cut-Off or Un-Shielded. Item #1b Total lumen calculations ,#1 c lighting area and option used from Table 401.1, Total lumen cap or Lumens allowed per Table 401.1 vs Total proposed Lumens. Item # 1c, Show all new as well as existing exterior luminaires in a lighting site plan. All exterior luminaires for this parcel must be included in the total lumen calculations. Item #1e Provide total luminaire quantity. Item # f. Special Inspection note. Please address Items # 1g and h. Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2012 Tucson/Pima County Outdoor Lighting Code, City of Tucson Commercial Plan Submittal Requirements |