Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM02054
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/11/2021 | DTRAMME1 | ENGINEERING | REVIEW | Passed | |
| 03/15/2021 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 03/23/2021 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 03/23/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A102; Floor Plan: Door 9 is not listed in the Door Schedule on Sheet A701. Please revise. 2. Sheet A102; Floor Plan: The door on the north wall does not have a number. Please provide and include in the Door Schedule on Sheet A701. 3. Sheet A102; General Notes: Note 5 references Sheet A700 for Wall Types. Please revise that reference. 4. Sheet A301; Roof Plan: The roof has a Key Note indicated, but no Key Note description is listed for that number. Please revise. 5. Sheet A701; Door Schedule: The Door Schedule is titled for the Cultural Kitchen. Please revise. 6. Sheet A701; Door Schedule: A Door Number 8 is indicated in this schedule. On what drawing is that door shown? 7. General: Please provide written responses to all review comments. |
| 03/24/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Public restrooms require mechanical exhaust. Provide a minimum exhaust flow rate of 50 CFM per water closet or urinal if the exhaust is continuous, 70 CFM if the exhaust is intermittent. Reference: Section 403.3.1.1 and Table 403.3.1.1, footnote g, IMC 2018 |
| 03/24/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Verify that the distance from the hot water source (WH2) to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018. |
| 03/24/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 04/01/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Provide plans and evidence on the plans that the proposed exterior lighting fully complies with the Outdoor Lighting Code. See section 104 for plan submittal requirements. Provide lighting plans with the following information on the plans; (a) Provide a complete luminaire schedule for each parcel, if more that one, include for each separate parcel. Include shielding and lamp color output temperature. (b) Size of the parcel in acres. It appears there are several parcels. If true, then provide total lumen calculations and all other required information for each parcel, per section 104.2.1. (c)See table 401.1, lighting area and option and indicate this information in the lighting site plan for each parcel, also show the locations and types of all exterior luminaires including existing. (d) Section 402.1 (light source color temperature requirements 3500K), shielding requirements, etc . (e) Provide a complete inventory (quantities) for each type of luminaire on the parcel. (f) Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2. (g) Specify any exceptions used. (h) Curfew lighting controls If applicable. Do not confuse the Outdoor Lighting Code with the IECC. #2. Provide compliance with the 2018 IECC for lighting. #3. Indicate conduit, conductor sizes and types for the panel feeders on the line diagram. Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2012 Tucson/Pima County Outdoor Lighting Code, City of Tucson Commercial Plan Submittal Requirements |
| 04/08/2021 | STEVE SHIELDS | ZONING | REVIEW | Passed |