Permit Number: T21CM01763
Parcel: 13633148C

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM01763
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/25/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. General: The two sets of structural calculations and canopy drawings would not allow the City of Tucson to apply an approval stamp on those sheets. It appears those documents have restricted access to 'Change the Document' or 'Adding Markups'. Please provide drawings and structural calculation sets that allow the City of Tucson to stamp for approval.
2. General: Please provide a Special Inspections Certificate with Parts A and B completed at this time. This certificate may be found at www.tucsonaz.gov/PDSD.
03/25/2021 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/06/2021 LOREN MAKUS ENGINEERING REVIEW Passed
04/06/2021 STEVE SHIELDS ZONING REVIEW Passed
04/14/2021 JPEELDA1 FIRE REVIEW Approved Plans are inconsitent. SOW might be a new shade/canopy. Please submit drawings that show the scope of work. Plans show two new buildings. If you have any questions please call or email me.
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033

Final Status

Task End Date Reviewer's Name Type of Review Description
04/07/2021 IMONSHI1 OUT TO CUSTOMER Completed