Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM01524
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/17/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | The current water calculations show a demand of 180 GPM; the maximum demand for a 1-1/2” meter is 100 GPM. [Second comment: The comment response letter states that a 1-1/2” meter serves the commercial suites but the water pressure calculations call out an existing 2-1/2” meter.] [Initial comment: Clarify the location and size of the Tucson Water meter serving the total fixture units noted in the water calculations on sheet P1.0. Reference: Section 107.2.1, IBC 2018.] |