Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T21CM01251
Parcel: 13315305A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM01251
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/17/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/17/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM01250, T21CM01251, T21CM01252, & T21CM01253
2200 N Camino Principal
Convert Restaurant to Residential Care

TRANSMITTAL: May 17, 2021
This site is located in the C-1 zone (UDC 4.7.20). Administrative and Professional Office is a permitted use in this zone (Table 4.8-4) Subject to Use Specific Standard 4.9.7.J.1, 3.d, .4, .6, & .8 and 4.9.13.O.

1. Zoning has reviewed the building plans but cannot approve until Development Package DP21-0041 has been approved Zoning cannot approved the building plans.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
05/18/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM01250-1253

GENERAL:
o Provide written responses to all review comments.
o Provide a complete plan set.
o Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Approved

ELECTRICAL REVIEW COMMENTS
Denied
E- No electrical issues, Cover sheet still references Fluorescent type fixtures, yet not in Lighting schedule. No action required.
E-2 No electrical issues
E-3 No electrical issues
E-4 No electrical issues
E-4.1 No electrical issues, Note #6 is unclear. No action required.
E-4.2 No electrical issues, Note #9 should be corrected. No Action required.
E-5 No electrical issues
E-.1 Should circuit 2nd floor or call out as copy of 1st floor. CO/smoke detectors not shown on 2nd floor
E-5.2 No electrical issues E-6 No electrical issues
E-6.1 Key Note #9 does not appear to be for a range.
Unit C 104 seems to be the ONLY unit with a CO / Smoke detector. Correct or clarify.
E-6.2 No electrical issues
E-7 No electrical issues, Should circuit 2nd floor or call out as a copy of 1st floor.
E-7.1 No electrical issues, Should circuit 2nd floor or call out as a copy of 1st floor.
E-7.2 No electrical issues, Should circuit 2nd floor or call out as a copy of 1st floor.
E-8 Need to provide calculated values for panel S.P. Did not find on Sheet E8.2 as stated.
E-8.1 No electrical issues
E-8.2 No electrical issues
E9 Where is panel S.P. on Single Line Diagram? If it is fed from 100 amp CB, the S.P., the panel S.P. panel is called out as 60 amp per panel schedule.
E-10 No electrical issues However specification for Fluorescent fixtures should be removed/updated to LED to match
Lighting Fixture Schedule. No action required.
E-11 No electrical issues
E-12 No electrical issues
E-13 Comcheck on sheet is unreadable. Hand calculation under light fixture IECC schedule would be accepted as proof of
compliance.


MECHANICAL REVIEW COMMENTS:
Approved

PLUMBING REVIEW COMMENTS:
Approved
05/24/2021 SBLOOD1 ENGINEERING REVIEW Approved