Permit Number: T21CM01036
Parcel: 14118002C

Address:
9800 E RITA RD

Review Status: Completed

Review Details: OTHER

Permit Number - T21CM01036
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/23/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet SP-001; Code Compliance: Note 1 references the Virginia Pool and Spa Safety Act. Please remove that note.
2. Sheet SP-001; Code Compliance: The IBC, IPC, IMC, and Energy Conservation Codes should reference the 2018 Editions. The NEC should reference the 2017 Edition.
3. Sheet SP-301: Please indicate the thickness of the splash pad on Sections 1 and 2 on this sheet.
4. General: Please provide a copy of the Special Inspections Certificate with Parts A and B completed.
5. General: Please provide a valuation (labor + materials) for this project.
02/23/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
02/23/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following Electrical Plan Review comments. Provide a written response.

Provide complete electrical plans sealed by a Registrant registered in the State of Arizona. ARS 32-125, Arizona Board of Technical Registration Rules R4-30-304.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/04/2021 PCAMARE1 OUT TO CUSTOMER Completed