Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T21CM01012
Parcel: 140280660

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM01012
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/22/2021 DTRAMME1 ENGINEERING REVIEW Passed
02/22/2021 JPEELDA1 FIRE REVIEW Approved
03/03/2021 STEVE SHIELDS ZONING REVIEW Approved
03/03/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/09/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Approved