Permit Number: T21CM00516
Parcel: 117121930

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM00516
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/19/2021 DTRAMME1 ENGINEERING REVIEW Passed
02/01/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Specify that all proposed plumbing fixtures shall be listed by a third-party certification agency as complying with the relevant standards. Reference: Section 303.4, IPC 2018.
02/01/2021 ROBERT SHERRY WATER REVIEW Completed
02/02/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Demonstrate energy code compliance for the building envelope using calculations based on the current code. Alterations of an existing, non-conditioned building space shall be brought into full compliance with the 2018 International Energy Conservation Code. Reference: Section C503.2, IECC 2018.
2. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C403.3.1, IECC 2018.
3. Show that the proposed HVAC equipment meets the minimum performance requirements of Section C403.3.2, IECC 2018.
02/08/2021 JPEELDA1 FIRE REVIEW Approved
02/09/2021 STEVE SHIELDS ZONING REVIEW Approved
02/09/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
02/16/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet G0.2; First Floor Life Safety Plan: Per the IBC Section 1017.3, the exit access travel distance shall be measured along the natural and unobstructed path of horizontal and vertical egress travel. Please revise.
2. Sheet G0.2; First Floor Life Safety Plan: A stair is indicated at the south end of this space, providing access to a new loft area. Please verify the exit access travel distance from the loft to the exit door. In addition, indicate the occupant load of the loft area.
3. Sheet A1.0; First Floor Plan: The Toilet Room 106 references an enlarged plan 5/S2.0. Please revise that reference.
4. Sheet A1.0; First Floor Plan: All interior elevatiions and sections reference Sheet S2.0. Please revise that reference.
5. Sheet A1.0; Loft Floor Plan: Please provide structural calculations for the loft floor framing.
6. General: Please provide written responses to all review comments.
02/16/2021 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed