Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM00516
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/19/2021 | DTRAMME1 | ENGINEERING | REVIEW | Passed | |
| 02/01/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Specify that all proposed plumbing fixtures shall be listed by a third-party certification agency as complying with the relevant standards. Reference: Section 303.4, IPC 2018. |
| 02/01/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 02/02/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Demonstrate energy code compliance for the building envelope using calculations based on the current code. Alterations of an existing, non-conditioned building space shall be brought into full compliance with the 2018 International Energy Conservation Code. Reference: Section C503.2, IECC 2018. 2. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C403.3.1, IECC 2018. 3. Show that the proposed HVAC equipment meets the minimum performance requirements of Section C403.3.2, IECC 2018. |
| 02/08/2021 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 02/09/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 02/09/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 02/16/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet G0.2; First Floor Life Safety Plan: Per the IBC Section 1017.3, the exit access travel distance shall be measured along the natural and unobstructed path of horizontal and vertical egress travel. Please revise. 2. Sheet G0.2; First Floor Life Safety Plan: A stair is indicated at the south end of this space, providing access to a new loft area. Please verify the exit access travel distance from the loft to the exit door. In addition, indicate the occupant load of the loft area. 3. Sheet A1.0; First Floor Plan: The Toilet Room 106 references an enlarged plan 5/S2.0. Please revise that reference. 4. Sheet A1.0; First Floor Plan: All interior elevatiions and sections reference Sheet S2.0. Please revise that reference. 5. Sheet A1.0; Loft Floor Plan: Please provide structural calculations for the loft floor framing. 6. General: Please provide written responses to all review comments. |
| 02/16/2021 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |