Permit Number: T21CM00405
Parcel: 116213590

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM00405
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/25/2021 DTRAMME1 ENGINEERING REVIEW Passed
01/27/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Specify that all owner furnished plumbing fixtures shall be listed by a third-party certification agency as complying with the relevant standards. Reference: Section 303.4, IPC 2018.
2. The fixture drain serving an automatic clothes washer shall connect to a fixture branch that is at least 3 inches in diameter. Reference: Section 406.2, IPC 2018.
3. Clarify how the new lavatory fixture has been vented in accordance with one of the methods shown in the IPC. Reference: Section 901.2.1, IPC 2018.
01/27/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Coordinate the plumbing and mechanical drawings with regard to the tag name of the new rooftop AC unit. Reference; Section 107.2.1, IBC 2018.
2. Ventilation for kitchens in private dwellings requires a minimum of 25 CFM (continuous operation) or 100 CFM (intermittent operation) of mechanical exhaust per room with no recirculation of air (e.g. specify the exhaust flowrate for the kitchen hood). Reference: Table 403.3.2.3, IMC 2018.
01/27/2021 ROBERT SHERRY WATER REVIEW Passed
02/04/2021 STEVE SHIELDS ZONING REVIEW Approved
02/08/2021 JPEELDA1 FIRE REVIEW Approved
02/08/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
02/16/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/16/2021 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed