Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T21CM00175
Parcel: 14041134D

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM00175
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/03/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Each wash basin in the restrooms has three lavatory faucets. Table C404.5.1, IECC 2018 shows a maximum piping length specifically for “Public lavatory faucets”; the column for “Other fixtures and appliances” is not applicable. What is the nominal size and length of the hose used to connect the water heater to the faucets? [Initial comment: Show how the installation of the tempered water for the two wash basins will comply with the maximum piping length for public lavatory faucets (i.e. what is the nominal size and length of the hose used to connect the water heater to the faucets). Reference: Section C404.5, IECC 2018.]