Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T21CM00175
Parcel: 14041134D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM00175
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/11/2021 JPEELDA1 FIRE REVIEW Approved
01/13/2021 DTRAMME1 ENGINEERING REVIEW Passed
01/25/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Show how the installation of the tempered water for the two wash basins will comply with the maximum piping length for public lavatory faucets (i.e. what is the nominal size and length of the hose used to connect the water heater to the faucets). Reference: Section C404.5, IECC 2018.
2. Provide tempered water for the public restroom lavatories using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2018.
3. Verify that the pipe sizes called out for the flush valves will not result in water velocities greater than that recommended by the pipe manufacturer (e.g. limit the water velocity to less than 8 FPS for copper piping). At a minimum design flow rate of 25 GPM for a siphonic, flush-valve water closet, a 1" Type L copper pipe has a flow velocity of 9.7 FPS. Reference: Table 604.3, IPC 2018.
01/25/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
01/25/2021 ROBERT SHERRY WATER REVIEW Completed
01/28/2021 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/28/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
02/01/2021 STEVE SHIELDS ZONING REVIEW Approved
02/10/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved