Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2021 JVINCEN1 FIRE REVIEW Approved
01/14/2021 DTRAMME1 ENGINEERING REVIEW Passed
01/20/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Show the drainage fittings installed to guide sewage in the direction of flow (e.g. branch connection from the mop sink and the double sanitary tee connecting the water closets in the women's restroom; the wall cleanouts). Reference: Section 706.3, IPC 2018.
2. Clarify how the hot water supplied to the restroom lavatories can be recirculated if the hot water return is reconnected to the hot water supply and not the hot water return pipe. Reference: Section 107.2.1, IBC 2018.
3. Revise the location of the sediment trap (detail 6/M4.1) to be downstream of the appliance shut off valve, as close to the equipment as possible. Reference: Section 408.4, IFGC 2018.
01/20/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
01/20/2021 ROBERT SHERRY WATER REVIEW Completed
01/26/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide compliance with the current 2018 IECC for the lighting.
2. Ref; Plan Sheet E4.1, Line Diagram. Provide the following information on the plan.
(a) Service disconnect and fuse sizes and types, AIC ratings for panels 'N1' and 'E2'.
(b) Available Fault Current at new 400 amp meter and disconnects.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.
02/02/2021 NICHOLAS ROSS ZONING REVIEW Approved
02/02/2021 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/03/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved