Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM00076
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/06/2021 | JVINCEN1 | FIRE | REVIEW | Approved | |
| 01/14/2021 | DTRAMME1 | ENGINEERING | REVIEW | Passed | |
| 01/20/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Show the drainage fittings installed to guide sewage in the direction of flow (e.g. branch connection from the mop sink and the double sanitary tee connecting the water closets in the women's restroom; the wall cleanouts). Reference: Section 706.3, IPC 2018. 2. Clarify how the hot water supplied to the restroom lavatories can be recirculated if the hot water return is reconnected to the hot water supply and not the hot water return pipe. Reference: Section 107.2.1, IBC 2018. 3. Revise the location of the sediment trap (detail 6/M4.1) to be downstream of the appliance shut off valve, as close to the equipment as possible. Reference: Section 408.4, IFGC 2018. |
| 01/20/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 01/20/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 01/26/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide compliance with the current 2018 IECC for the lighting. 2. Ref; Plan Sheet E4.1, Line Diagram. Provide the following information on the plan. (a) Service disconnect and fuse sizes and types, AIC ratings for panels 'N1' and 'E2'. (b) Available Fault Current at new 400 amp meter and disconnects. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |
| 02/02/2021 | NICHOLAS ROSS | ZONING | REVIEW | Approved | |
| 02/02/2021 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 02/03/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved |