Permit Number: T21BU00373
Parcel: 11504475B

Review Status: Completed

Review Details: POOL - COMM MODEL

Permit Number - T21BU00373
Review Name: POOL - COMM MODEL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/30/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. General: Please provide a typical enlarged, dimensioned terrace space plan indicating the spa placement and clearance requirements for the spa covers (per the Specifications Page 3). Will covers be included on all spas?
2. General: Please include details indicating how the spa is connected to the support system. In addition, verify the support system is capable of supporting the spa loads as described in the Specifications Page 18. Provide structural calculations as required.
3. General: Please provide a project valuation (labor + materials) for the 15 new spa units.
4. General: Please provide written responses to all review comments.
08/02/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
08/02/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide enlarged plans showing the location of the water supply (i.e. hose bibb) and the discharge point for draining the spas. The spas shall drain to the sanitary drain system. Reference: Section 107.2.1, IBC 2018.
08/02/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following Electrical plan review comments. Also provide a written response.

Provide Sealed electrical plans, design and calculations performed by an Arizona registrant who has demonstrated proficiency through registration, education, technical knowledge, or experience to perform such work.

Include load calculations ,complete panel schedules, power source.

Compliance with 2017 NEC art 680 part 4.

Verify 2012 Tucson/Pima County Outdoor Lighting Compliance for the LED spa luminaires. Section 401.2.1(2).

Ref; 2018 IBC 107.2.1, 2017 NEC. City of Tucson Commercial Plan/Permit Submittal Requirements. 2012 Tucson/Pima County Outdoor Lighting Code.
08/17/2021 NROSS1 ENGINEERING REVIEW Passed
08/17/2021 NICHOLAS ROSS ZONING REVIEW Approved