Permit Number: T20CM09082
Parcel: 123050400

Address:
2156 E EDISON ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T20CM09082
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/04/2021 NMARTEL1 ZONING REVIEW Reqs Change PDSD TRANSMITTAL
Nicholas Martell, Planner
T20CM09082
Residential Addition
February 04, 2021

The residential plans have been reviewed by the Zoning Review Section but cannot be approved until all zoning comments or concerns have been addressed.
1. Please revise the site plan with more consitency and explanation by addressing the following:
a. Provide a legend of symbols that is consistent throughout the plan. For instance, there are several dashed lines on the site plan that are unlabeled. Please show a legend demonstrating their purposes.
b. Aerials show a small structure that was built around 2014, adjacent to the guest house, that appears to be unpermitted. It appears that there is a dashed line on the proposed site plan where that structure is. Indicate the nature of that structure, and whether or not it will remain. Additionally, please show the setbacks for that structure, as it appears close to the property line.
c. There is a rectangular structure or feature just south of the main house shown on the proposed plan. Zoning is unable to determine the nature of that structure or feature.
d. Please ensure all aspects of the plan are clearly labeled
e. For reference, the guest house with a full kitchen will be considered an entire second unit unless shown otherwise. This does not impact the site plan, as the unit has been present for several years.

If you have any questions about this transmittal, contact me at Nicholas.Martell@tucsonaz.gov
12/28/2020 LBOWERS1 BUILDING-RESIDENTIAL REVIEW Reqs Change Provide a complete plan set showing 2018 IRC compliance review.

Structures require a clear 3 foot fire separation distance to the property line unless the structure includes a one-hour rated wall. See IBC Table 721.1(2), Items 15-1.1 to 16-1.3 for a listing of fire rated materials.
12/28/2020 LBOWERS1 ENGINEERING REVIEW Needs Review