Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T20CM08647
Parcel: 11506089A

Address:
1990 N 7TH AV

Review Status: Completed

Review Details: OTHER

Permit Number - T20CM08647
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/13/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide a site plan showing the location of the relocated electrical service on the premises.
2. Provide a complete line diagram showing:
(a) Voltage and Phase.
(b) Available fault current supplied through the utility, and AIC ratings of the electrical service and downstream equipment. Be advised, if the available fault current exceeds 22K the plans will need to sealed by an Electrical Engineer registered in the State of Arizona.
(c) Complete grounding detail including Water, Gas, Building steel. Including all ground conductor sizes per NEC art 250, as applicable.
(d) Indicate panel 'A' as existing.
(e) Fuse sizes and types.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/14/2021 IMONSHI1 OUT TO CUSTOMER Completed