Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T20CM08554
Parcel: 140160130

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T20CM08554
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/11/2021 ANDREW CONNOR NPPO REVIEW Passed
01/12/2021 SROGERS2 ENGINEERING REVIEW Passed
01/12/2021 SAMUEL ROGERS ZONING REVIEW Reqs Change FROM: Samuel Rogers
PDSD Zoning Review Section

PROJECT: T20CM08554
Room Addition – T20DV05866 (1st Review)
5250 S Campbell Av St. #14

TRANSMITTAL DATE: 1/12/2021

DUE DATE: 11/06/2020

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


01. COMMENT: A plot plan showing the location of the addition on the addition is required. A minimum of 3’ is required on the sides of the proposed addition (measured from the addition to the lot line). A plot plan template can be found here: https://www.tucsonaz.gov/files/pdsd/forms/Mobile_Homes_Plot_Plans.pdf


If you have any questions about this transmittal, Contact Samuel Rogers at Samuel.Rogers@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans
01/12/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building.

Place each plan sheet into a single PDF file for reviewing as a complete plan set.

Use the Residential Plan Requirements & Checklist at https://www.tucsonaz.gov/pdsd/residential-permits

Sample plans are available at https://www.tucsonaz.gov/pdsd/residential-permits

SITE PLAN:

Provide a site plan showing all buildings, R106.1.1. Show setbacks to property lines and location of utility lines to the building.

FLOOR PLAN:

Provide a floor plan showing each room with labeled function. Show window sizes and identify type as XO or SH.

Show existing rooms with windows opening into the addition. Bedrooms require direct exterior egress.

FRAMING PLAN:

Provide a roof framing plan showing beam and rafter location and sizes.

SECTIONS - DETAILS:

Provide structural details showing code compliant materials and fasteners from the foundation to the roof covering of new exterior walls. Include the foundation dimensions and floor separation from grade. Show rating of insulation both walls and ceiling. New exterior walls require compliant attachment to a foundation with minimum 6" spacing above exterior grade.

MECHANICAL PLANS:

Provide equipment details showing code compliant components, locations and sizes, or show relocated components.

ELECTRICAL PLANS:

Provide wiring details showing code compliant devices and sizes. Show circuit number and size with receptacles at all walls and lighting control at each doorway both interior and exterior. Receptacle, lighting and smoke detector circuits require arc-fault protection.

INTERNATIONAL ENERGY CONSERVATION CODE:

Provide insulation details minimum (R-13 walls and R-38 ceiling) showing code compliant placement of materials and ratings, N1101. Windows require a solar heat gain of 0.25 or better.

OUTDOOR LIGHTING CODE

Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations or show proposed fixtures as Full Cut Off (night sky friendly).

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review