Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T20CM08400
Parcel: 140160130

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM08400
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/10/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T20CM08400
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

Consolidate pages of construction plans into a single .PDF file as prescribed at the PDSD web site. https://www.tucsonaz.gov/pdsd/online-permits

Sample plans are available at https://www.tucsonaz.gov/pdsd/residential-permits

GENERAL COMMENTS:

1. Show code references as recognized by the City of Tucson. Adopted 2018 codes are listed at the Planning & Development Services web site. Add the code references used for the design to the plans.

SITE PLAN:

1. Indicate the location and size of buildings, utility meters and gas, water, electric and sewer or septic lines from property line to building, R106.1.1. Show the point of connection of proposed lines to the utility (electrical) service for verifying correct sizes and necessary upgrades.

FOUNDATION PLANS:

1. Framed exterior walls of enclosed roof structures require continuous concrete footings of minimum 12” width and 12” below the undisturbed ground surface, R403.1.
2. Locate and specify all anchor-bolt spacing on the foundation plan. Minimum ½” diameter with (anchor bolt length for assuring) 7” embedment into concrete or masonry, R403.1.6. Maximum spacing 6’ o/c and within 12” of each sill plate end, R403.1.6.

FLOOR PLANS:

1. Clarify if any dwelling windows are blocked or opening into the storage room on the floor plan, R106.1.1.

SECTIONS - DETAILS:

1. Specify the type of structural siding, R602.10.3.4, and a #15 water-resistive barrier over studs of all exterior walls, R703.2. .
2. Show the exterior sheathing with a minimum clearance 4” above grade or 2” above paved areas, R703.7.2.1. Consider a design with concrete stems.

ELECTRICAL PLANS:

1. Show at least one wall-switch-controlled lighting outlet providing illumination on the exterior side of each egress door having grade level access R3903.3.

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
02/19/2021 STEVE SHIELDS ZONING REVIEW Approved