Permit Number: T20CM07870
Parcel: 140130400

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T20CM07870
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/30/2020 NMARTEL1 ZONING REVIEW Reqs Change PDSD TRANSMITTAL
Nicholas Martell, Planner
T20CM07870
Garage Conversion
November 30, 2020

The residential plans have been reviewed by the Zoning Review Section but cannot be approved until all zoning comments or concerns have been addressed.

1. Please resubmit the plans following commercial parking requirements. For any single-family dwelling in the R-1 with five bedrooms, three parking spaces are required. For every bedroom over five, one additional space is required for each (4.9.7.B.7 UDC). According to the submitted plans, 4 commercial parking spaces are required. Parking spaces may not be located in a vehicular use area in any front street perimeter yard.

If you have any questions about this transmittal, please contact me at Nicholas.Martell@tucsonaz.gov
11/30/2020 SBLOOD1 ENGINEERING REVIEW Passed
12/10/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T20CM07870
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

Consolidate pages of construction plans into a single .PDF file as prescribed at the PDSD web site. https://www.tucsonaz.gov/pdsd/online-permits

SECTIONS - DETAILS:

1. Show a cross-section detail of the new exterior wall with a minimum 12” footing depth below the undisturbed ground surface R403.1. Show the anchor bolt with 3” clearance from earth, R403.1.3.5.3.
2. Specify the minimum thickness (1/2”) of non-structural siding, R602.10.3.4, and a #15 water-resistive barrier over studs/sheathing of all exterior walls, R703.2. OSB may be 3/8” thickness as a structural sheathing, whereas T1-11 is non-structural.
3. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38 or R-30 for an addition up to 500 SF.

ELECTRICAL PLANS:

1. Show at least one wall switch controlled light at outdoor entrances or exits, E3903.3.
2. Protect extended branch circuits with combination type arc-fault circuit interrupters, or an AFCI type receptacle at the first outlet on the branch circuit, E3902.17.

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review