Review Date Reviewer's Name Type of Review Description Status Comments
10/27/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/27/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide guards for equipment located within 10 feet of a roof edge or of a walking surface that is elevated more than 30 inches above the adjoining grade. Reference: Section 304.11, IMC 2018.
2. Show the routing and termination of the condensate drain for FCU-01. Reference: Section 307.2.1, IMC 2018 as amended by the City of Tucson.
3. Verify that the termination of exhaust fans EF-1 and EF-3 are more than 30 feet from the property line. Reference: Section 501.3.1 (1), IMC 2018.
4. Clarify the specifications for the exhaust fans and provide a basis for the design (e.g. Manufacturer, model, wheel size, etc.) Note: a direct drive fan is not arrangement 10, it is arrangement 4. Reference: Section 107.2.1, IBC 2018.
10/27/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide a GFI protected 120volt maintenance receptacle on the roof for the new mechanical equipment per NEC 210.63.
2. The one-line diagram is confusing. Most of the equipment in bold has the letter 'N' next to them which would normally indicate 'NEW'. Yet the title lettering at A1 DETAIL states "EXISTING", and the WIRE AND CONDUIT SCHEDULE show all the feeders as existing… Please clarify.
3. Please provide a detailed description of the scope of work proposed.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. 2012 Tucson/Pima County Outdoor Lighting Code.
10/27/2020 ROBERT SHERRY WATER REVIEW Passed
10/27/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet G101; Code Review (Occupancy Classification): Per the IBC Section 414.1.3, please provide a report on these drawings for the expected quantities of hazardous materials to be stored in this space.
2. Sheet G101; Code Review (Occupancy Fire Separation): Please indicate on this sheet the IBC Table 721.1(2) Item Number for the fire resistant rated assembly.
3. Sheet G101; Code Floor Plan: A note on this plan indicates to provide a fire stop system for all thru wall penetrations. Please add a reference to the IBC Section 714.4.1.2 to that note.
4. General: Please verify the ventilation requirements of the IBC Section 414.3 are met and indicated on these drawings.
5. General: Please verify the explosion control requirements of the IBC Section 414.5.1 are met and indicated on these drawings.
6. General: Please verify the emergency/standby power requirements of the IBC Section 414.5.2 are met and indicated on these drawings.
7. General: Please verify the spill control requirements of the IBC Sections 414.5.3 and 415.9.1.4 are met and indicated on these drawings.
8. General: Please verify the emergency alarm requirements of the IBC Sections 415.5 and 415.9.1.5 are met and indicated on these drawings.
9. General: Please verify the requirements of the IBC Section 415.8 do not necessitate a detached building, and indicate on these drawings.
10. General: Please provide written responses to all review comments.
10/27/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
10/28/2020 DTRAMME1 ENGINEERING REVIEW Passed
10/29/2020 MALLORY RESS ZONING REVIEW Approved
11/10/2020 JVINCEN1 FIRE REVIEW Approved