Review Date Reviewer's Name Type of Review Description Status Comments
10/27/2020 SBLOOD1 ENGINEERING REVIEW Passed
10/27/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T20CM07354
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration

GENERAL COMMENTS:

1. Items built without permit may require alteration or improvement for achieving code compliance with the 2018 IRC, R105. Building structure loads may not bear upon a manufactured structure without an engineer’s analysis, R106.1.1.

FOUNDATION PLANS:

1. Show exterior footings at least 12” below the undisturbed ground surface, R403.1.4.
2. Concrete footings require a minimum 12” width with appropriately placed rebar reinforcement, R403.

STRUCTURAL PLANS:

1. Show girder/beam sizes with appropriate load carrying capacity, R301.1.
2. Provide an engineer’s calculation, design and seal for a performance design when minimum sizes are not code compliant with the IRC, R301.1.

If you have any questions, please contact:
Ken Van Karsen
(520) 791-5550
City of Tucson Residential Plan Review