Permit Number: T20CM07297
Parcel: 125091060

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM07297
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/23/2020 LOREN MAKUS ENGINEERING REVIEW Passed
10/26/2020 JPEELDA1 FIRE REVIEW Approved
10/26/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet G0.0; Project Information; Project Description: The Project Information indicates a new 423 SF canopy, while the Project Description indicates interior work only. Please clarify.
2. Sheet G0.0; Architectural Site Plan: This plan indicates the new canopy extending to the property line. The City of Tucson requires the roof projection of the canopy to be a minimum of 2'-0" from the property line, and the face of the structural supports of the canopy to be a minimum of 5'-0" from the property line. Please indicate this on the Site Plan.
3. Sheet G0.0; Architectural Site Plan: The new canopy indicates 423 SF, but depicts a 15'-7" x 24'-1" footprint (376 SF). Please coordinate.
4. Sheet G0.0; Sheet Index: Please revise the G sheets in the Sheet Index to match the actual sheet numbers.
5. Sheet G2.0; Code Review (Actual Area): Where did the 2337 SF come from? Please coordinate with Sheet G0.0 (1727 SF).
6. Sheet G2.0; Code Review (Common Path of Egress): Reference is made to the IBC Section 1014.3. Please revise that reference.
7. Sheet G2.0; Code Review (Travel Distance): Reference is made to the IBC Table 1016.2. Please revise that reference.
8. Sheet G2.0; Code Review: Many of the IBC references in this Code Review are not consistent with the 2018 IBC. Please revise.
9. Sheet A1.0; Wall Type 'B' Detail: Per the IBC Section 1607.15, interior partitions must be able to resist a 5 PSF horizontal load. Please indicate lateral bracing at the top of the partition, indicating the bracing size and spacing, as well as the connection of the bracing to the top of the partition and to the structure above.
10. Sheet A2.0; Canopy: Please provide structural calculations for the canopy.
11. Sheet A2.0; Canopy: Please provide structural general notes on this sheet for the canopy material strengths, design loads, etc.
12. General: Please provide written responses to all review comments.
10/26/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/23/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide designated branch circuits and panel for the electrical devices.
2. Show location of the panel.
3. Provide a luminaire schedule or complete description of the Proposed luminaires.
4. Provide full compliance with the 2012 Tucson/Pima County Outdoor Lighting Code.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. 2012 Tucson/Pima County Outdoor lighting Code.
12/17/2020 STEVE SHIELDS ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Steve Shields
Section Manager

PROJECT: T20CM07297
2719 E Broadway Blvd
Office TI & Add Shade Structure

TRANSMITTAL DATE: December 17, 2020

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. Zoning cannot approve the building plans until all other PDSD review agencies have approved.

2. A Development Package must be submitted and approved before the building plans can be approved. This DP shall meet the requirements of checklist for Minor Changes to Commercial/Industrial sites found at: https://www.tucsonaz.gov/files/pdsd/forms/Minor_Changes_to_Commercial_Industrial_Sites_.pdf

If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov