Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T20CM06818
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/07/2021 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Approved | |
| 01/07/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/15/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Comment not resolved; the note on sheet A1.0 refers to the plumbing plans for information about the plumbed water cooler. Show the specifications on the plan set. [Initial comment: Provide specifications for the "plumbed water cooler" noted on sheet A1.0 (P6). The use of a point-of-use water dispenser in lieu of a drinking fountain requires the installation of a listed and labeled dispenser along with a permanently mounted disposable cup dispenser. The cup dispenser shall be located adjacent to the water dispenser with the dispensing end between 34" and 48" above the finished floor.] |
| 12/15/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 12/16/2020 | JPEELDA1 | FIRE | REVIEW | Approved | Per Tucson Water model dated 11-20-2020 they meet the fire flow requirements and do not require fire sprinklers. |