03/21/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please be advised that the electrical line diagram calls for panels to have MLO. And the panel schedules show Main Breaker. Also this comment applies to the other Tenant panels.
2018 IBC 107.2.1, 2017 NEC