Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T20CM06293
Parcel: 141114050

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM06293
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

Ref; Plan sheet LSP.

1 . The site lighting plan for the parcel shows 12 existing exterior ā€˜D’ type luminaires. The Outdoor Lighting Lumen Schedule shows only 9 existing ā€˜D’ luminaires. Please clarify .

2. Update the Outdoor Lighting Calculations to reflect any exterior lighting changes.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, 2012 Tucson/Pima County outdoor Lighting Code.
02/07/2022 DBENOIT1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Reqs Change
12/13/2021 JPEELDA1 FIRE REVIEW Approved
12/14/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/28/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Comment not resolved. The drawing numbers in the sheet index are different from the numbers on the plumbing drawings and there are two drawings labeled P-2 and P-3. [Initial comment: Coordinate the drawing numbers with the sheet index on sheet A-1.]
12/28/2021 ROBERT SHERRY WATER REVIEW Completed
12/28/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Coordinate the components listed in the COMcheck envelope compliance with the components shown on the drawings (e.g. the insulation of the walls and ceiling of the office).

Final Status

Task End Date Reviewer's Name Type of Review Description
02/07/2022 DBENOIT1 APPROVAL SHELF Completed
02/07/2022 DBENOIT1 OUT TO CUSTOMER Completed
02/07/2022 DBENOIT1 REJECT SHELF Completed