Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T20CM06291
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/10/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Wall insulation on drawing unchanged, no insulation called out for ceiling (see A-3.1). [Initial comment: Coordinate the components listed in the COMcheck envelope compliance with the components shown on the drawings (e.g. the insulation of the walls and ceiling of the office).] |
| 02/10/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Comment not addressed. [Initial comment: The rim elevation of the next upstream sanitary manhole (2936.70') is 12" or more below the first floor elevation (2937.84'). A backwater valve shall not be installed. Reference: Section 714.1, IPC 2018, as amended by the City of Tucson.] |
| 02/23/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. Outdoor lighting question per the previous electrical review could not be verified because lighting plans for building #7 and #8 were not submitted in the resubmitted plan set. The reviewer could not correlate the āDā type exterior lighting on these buildings. Please resubmit complete power and lighting plans next resubmittal. Ref; 2018 IBC sec 107.1, 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. |
| 03/02/2022 | LSHAMIS1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |