Permit Number: T20CM06291
Parcel: 141114050

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM06291
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/10/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Wall insulation on drawing unchanged, no insulation called out for ceiling (see A-3.1). [Initial comment: Coordinate the components listed in the COMcheck envelope compliance with the components shown on the drawings (e.g. the insulation of the walls and ceiling of the office).]
02/10/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Comment not addressed. [Initial comment: The rim elevation of the next upstream sanitary manhole (2936.70') is 12" or more below the first floor elevation (2937.84'). A backwater valve shall not be installed. Reference: Section 714.1, IPC 2018, as amended by the City of Tucson.]
02/23/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

Outdoor lighting question per the previous electrical review could not be verified because lighting plans for building #7 and #8 were not submitted in the resubmitted plan set. The reviewer could not correlate the ā€˜D’ type exterior lighting on these buildings. Please resubmit complete power and lighting plans next resubmittal.

Ref; 2018 IBC sec 107.1, 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements.
03/02/2022 LSHAMIS1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review