Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T20CM06291
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/03/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. Ref; Plan sheet LSP. 1 . The site lighting plan for the parcel shows 12 existing exterior āDā type luminaires. The Outdoor Lighting Lumen Schedule shows only 9 existing āDā luminaires. Please clarify . 2. Update the Outdoor Lighting Calculations to reflect any exterior lighting changes. Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, 2012 Tucson/Pima County outdoor Lighting Code. |
| 02/07/2022 | DBENOIT1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 12/13/2021 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 12/14/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/28/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Comment not resolved. The drawing numbers in the sheet index are different from the numbers on the plumbing drawings and there are two drawings labeled P-2 and P-3. [Initial comment: Coordinate the drawing numbers with the sheet index on sheet A-1.] 2. The rim elevation of the next upstream sanitary manhole (2936.70') is 12" or more below the first floor elevation (2937.84'). A backwater valve shall not be installed. Reference: Section 714.1, IPC 2018, as amended by the City of Tucson. |
| 12/28/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 12/28/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Coordinate the components listed in the COMcheck envelope compliance with the components shown on the drawings (e.g. the insulation of the walls and ceiling of the office). |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/07/2022 | DBENOIT1 | APPROVAL SHELF | Completed |
| 02/07/2022 | DBENOIT1 | OUT TO CUSTOMER | Completed |
| 02/07/2022 | DBENOIT1 | REJECT SHELF | Completed |