Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T20CM06289
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/08/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | See T20CM06297 for mechanical comments |
| 02/08/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 02/23/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. Outdoor lighting question per the previous electrical review could not be verified because lighting plans for building #7 and #8 were not submitted in the resubmitted plan set. The reviewer could not correlate the āDā type exterior lighting on these buildings. Please resubmit complete power and lighting plans next resubmittal. Ref; 2018 IBC sec 107.1, 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. |
| 03/02/2022 | LSHAMIS1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |