Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T20CM06162
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/13/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | The structural calculations are based on a total weight of 525 pounds for the water heater, but the dry weight of the water heater is approximately 166 pounds, not 105 pounds. Also, the calculations call for specific connections for the studs at the base plate and at the roof joist connection. While detail T5/S1.1 shows the roof joist connection, nothing on the drawing set indicates that this detail applies to the water heater installation and nothing on the drawings shows the base plate connection. [Initial Comment: Provide structural calculations for the mounting shelves for the water heaters (labeled WH-2 in detail 1/P2.0) to show that the water heaters will be safely supported from the building structure. Reference: Section 301.2, IPC 2018.] |
| 12/13/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 12/14/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/14/2021 | NGARCIA3 | OUT TO CUSTOMER | Completed |