Permit Number: T20CM06162
Parcel: 117141360

Address:
141 W SIMPSON ST

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T20CM06162
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/23/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/23/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections R302.2 and R403.7, IECC 2018 as amended by the City of Tucson.
2. Secure the refrigerant circuit access ports of the condensing units to prevent unauthorized access. Reference: Section 1101.10, IMC 2018.
11/23/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Clarify the plumbing fixture schedule; it calls for the fixtures being for "floors 1-6." Reference: Section 107.2.1, IBC 2018.
2. Verify the specifications for the water heaters (WH-1). The schedule calls for 50-gallon water heaters. Reference: Section 107.2.1, IBC 2018.
3. Provide structural calculations for the mounting shelves for the water heaters (labeled WH-2 in detail 1/P2.0) to show that the water heaters will be safely supported from the building structure. Reference: Section 301.2, IPC 2018.
12/06/2021 PCAMARE1 ELECTRICAL-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/07/2021 VVERA1 OUT TO CUSTOMER Completed