Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T20CM06162
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/23/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
11/23/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections R302.2 and R403.7, IECC 2018 as amended by the City of Tucson. 2. Secure the refrigerant circuit access ports of the condensing units to prevent unauthorized access. Reference: Section 1101.10, IMC 2018. |
11/23/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Clarify the plumbing fixture schedule; it calls for the fixtures being for "floors 1-6." Reference: Section 107.2.1, IBC 2018. 2. Verify the specifications for the water heaters (WH-1). The schedule calls for 50-gallon water heaters. Reference: Section 107.2.1, IBC 2018. 3. Provide structural calculations for the mounting shelves for the water heaters (labeled WH-2 in detail 1/P2.0) to show that the water heaters will be safely supported from the building structure. Reference: Section 301.2, IPC 2018. |
12/06/2021 | PCAMARE1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
12/07/2021 | VVERA1 | OUT TO CUSTOMER | Completed |