Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T20CM06162
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/10/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A-301: A note in the title block indicates "Preliminary Not For Construction". Please remove that note and add the architect's seal. 2. Sheet A-301; Wall Section 1: The footing depth is indicated as "T" Per Footing Schedule. Please provide the footing depth and footing width on this detail (no structural sheets were included in this revision). 3. Sheet A-301; Wall Section 1: Please add a note for the continuous reinforcing in the footing (no structural sheets were included in this revision). 4. Sheet A-301; Wall Section 1: The bearing wall stud has a note indicating "Wood Stud Wall-See Structural". Detail 6.4/A-500 could be used as a reference in that note (no structural sheets were included in this revision). 5. Sheet A-501; Detail 1: The bearing wall stud has a note indicating "Wood Framed Wall See Structural". Please revise that note (no structural sheets were included in this revision). 6. General: Please provide written responses to all review comments. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/12/2021 | VVERA1 | OUT TO CUSTOMER | Completed |