Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T20CM05882
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/01/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet T-1.0; Project Information; Scope of Work: The 'Occupancy' indicated Family Dwelling, and the 'Scope of Work' indicated New Residence. The Occupancy Classification should be considered as a Group Home facility (reference the IBC Section 310.4). 2. Sheet T-1.0; Inclusive Home Design Notes: The Group Home facility shall meet the requirements of the 2018 IBC and the 2009 ICC/ANSI A117.1 Accessibility Code. Please indicate that on this sheet. In addition, remove the Inclusive Home Design notes. 3. Sheet T-1.0; General Notes (1): Please revise the code to the 2018 IBC. In addition, include the 2018 IPC, 2018 IMC, 2017 NEC, 2018 IFC, 2018 IECC, and the 2009 ICC/ANSI A117.1 Accessibility Code. 4. Sheet A-1.0; General Notes (1): Please revise per Comment 3. 5. Sheet A-1.0; Project Information; Scope of Work: Change these to indicate a new Group Home facility. 6. Sheet A-1.0: Please indicate on this sheet calculations for the Occupant Load (IBC Table 1004.5), and for the Required Plumbing Fixtures (IBC Table 2902.1). 7. Sheet A-1.0: Please provide the Allowable Building Height (IBC Tables 504.3 and 504.4), and the Allowable Building Area (IBC Table 506.2) on this sheet. 8. Sheet A-1.0: Please indicate an automatic sprinkler system is required per the IBC Section 903.2.8. 9. Sheet A-1.0: Per the IBC Section 420, please indicate the fire resistance rating separations required, including a U.L. Listing Number for each assembly 10. Sheet A-1.0: Per the IBC Section 1019, please indicate the fire resistance rating required at the exit access stairway, including a U.L. Listing Number for that assembly. 11. Sheet A-1.0: Please provide an analysis for the Exit Access Travel Distance per the IBC Section 1017. 12. Sheet A-1.0: Please indicate accessibility requirements per the IBC Sections 1107.6.3 and 1107.7, and the ICC/ANSI A117.1 Chapter 10. 13. Sheet A-2.2; Light, Ventilation, and Heating Note: Please revise these notes as required to apply to a commercial building. 14. Sheet A-2.2; Emergency Escape and Rescue Openings: Please revise these notes as required to apply to a commercial building (IBC Section 1030). 15. Sheet A-3.1; Inclusive Home Design Ordinance: Please remove these notes since this is a commercial building. 16. Sheet A-3.2: Please revise these schedules as required for a commercial building. 17. Sheet A-4.0; ICF Screen Grid Notes: Please revise/remove these notes as required for a commercial building. 18. Sheet A-5.4; Handrail Notes: Please revise/remove these notes as required for a commercial building. 19. Sheet A-6.0; Loads on Roof Trusses: Please revise these notes as required for a commercial building per the IBC Chapter 16. 20. Sheet R-6.2; IRC Code Sections: Please revise this sheet number, and revise the sheet as required for a commercial building. 21. Sheet A-7.1; Restroom Notes: Please revise these notes as required for a commercial building. 22. Sheet A-8.0: Please add a note on this sheet that references the IBC Section 107.3.4.1 for deferred submittals. 23. Sheet A-8.0; IRC Table R301.5: Please remove this table. 24. General: All sheets must be sealed, signed, and dated by a Registered Design Professional per the IBC Section 107. 25. General: Please provide structural calculations, material properties, drawings, and general notes. 26. General: Please provide a Special Inspections Certificate with Parts A and B completed. This form may be found at www.tucsonaz.gov/PDSD. 27. General: Please provide written responses to all review comments. |