Permit Number: T20CM05683
Parcel: 123060210

Address:
2093 E LEE ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM05683
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/15/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Completed
10/29/2020 LOREN MAKUS ENGINEERING REVIEW Passed
10/30/2020 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Section Manager

PROJECT: T20CM05683
2093 E Lee St
New SFR
Residential (2nd Review)

TRANSMITTAL DATE: October 30, 2020

This site is located in the R-1 zone (UDC 4.7.1). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10.

1. As this R-1 lot does not support two (2) dwelling units remove all references to “FUTURE RESIDENCE” as it is not allowed.

2. Provide elevations for the proposed 8’ Trellis.


COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).

This site is located in the R-1 zone (UDC 4.7.1). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10.

Per UDC Article 6.4.5.B perimeter yard setbacks are based on a measurement from the highest point of the exterior wall measured to design grade.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure’s wall facing each interior property line (Table 6.3-2.A).

1. Based on a wall height of 11’-0” the required perimeter yard setback from the west side of the house to the west property line is 7’-4”, proposed setback is 6’-0”

2. Based on a wall height of 11’-0” the required perimeter yard setback from the north side of the house to the north property line is 7’-4”, proposed setback is 6’-0”

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956