Permit Number: T20CM04388
Parcel: 115150400

Address:
443 W PLATA ST

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T20CM04388
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/20/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
07/20/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide the number of drinking fountains that complies with the requirements of Sections 2902.1and 2902.5, IBC 2018 and Section 410.3, IPC 2018.
2. Revise the site plan to show the location and termination of the building sewer as noted on sheet P1. Reference: Section 107.2.1, IBC 2018.
3. The rim elevation of the next upstream sanitary cleanout (9460*02) is approximately 2368', which is the same as the first floor elevation (2368'). Provide a backwater valve per Section 714.1, IPC 2018, as amended by the City of Tucson.
4. Clarify the arrangement of the crickets along the east-west parapet extensions shown on the roof plan of sheet A1.0: the crickets do not terminate at the end the parapet extensions unlike those shown on the mechanical roof plan on sheet M1.
5. Provide secondary (overflow) roof drainage. Reference: Sections 1108.1, 1108.2 and 1108.3, IPC 2018.
07/20/2020 ROBERT SHERRY WATER REVIEW Completed
07/23/2020 JPEELDA1 FIRE REVIEW Approved
07/27/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Ref; Cover plan sheet. Revise the reference to 2012 NEC to the currently adopted 2017.
2. Revise the IECC calculations to the current 2018.
3. Ref; Plan sheets E1 and E2. The Outdoor lighting calcs on each plan do not correlate with each other.
4. Provide a complete luminaire schedule for all the lighting that also correlates with the Outdoor lumen calcs for exterior lighting.
5. Verify luminaire lamp output color temperature to comply with sec 402.1 of the Outdoor Lighting Code. 3500K.
6. Provide a note on the plan requiring a Special Inspection for Outdoor Lighting required if applicable per section 104.2.2, 106.2.1.
7. Indicate whether the new service overhead or underground fed by the utility. Comply with 2018 IBC Amendments sec 112.1.1.
8. Verify that the sequence of operation for the exhaust fans complies with the Mechanical requirements. See Mechanical plan.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code.
08/07/2020 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Section Manager

PROJECT: Silver Street Warehouse
T20CM04388

TRANSMITTAL DATE: August 7, 2020

1. Zoning has reviewed the building plans for compliance with the development package DP20-0072. While the building plans are consistent with the DP as it relates to the zoning review purview of the building footprint, building height, square footage, site conditions etc., zoning cannot approve the building plans until the DP is approved and all PDSD Commercial Plans reviewers have approved the building plans.


If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
08/13/2020 LOREN MAKUS ENGINEERING REVIEW Reqs Change The Development Package must be approved first.
08/31/2020 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Reqs Change Reviewer: Chris Anderson
BUILDING – COMMERCIAL
1. Please respond to all review comments in writing.
2. Please submit structural calculations that are unsecured so that the City reviewer’s stamp can be placed on them. Ref. 2018 IBC 107.2.1.
3. Submit a filled out City of Tucson Special Inspections Certificate.
4. Roof insulation shown on the Building Section A/A2.0 does not match the roof insulation shown on detail 8/SD1; neither of which match the prescriptive insulation for metal buildings shown in 2018 IECC Table C402.1.3. Coordinate.
5. The exterior wall insulation shown in the Wall Legend, sheet A1.0, does not match the prescriptive wall insulation for mass walls shown in 2018 IECC Table C402.1.3.
6. Submit a building envelope COMcheck since the prescriptive insulation methods of 2018 IECC Table C402.1.3 are not being used and add the U-factors and for exterior wall fenestration (swing doors) used in the COMcheck to the Door schedule on sheet A3.0.
08/31/2020 JGARCIA1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
08/31/2020 JGARCIA1 APPROVAL SHELF Completed
08/31/2020 JGARCIA1 OUT TO CUSTOMER Completed