Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T20CM04375
Parcel: 13733913A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM04375
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/13/2020 JPEELDA1 FIRE REVIEW Approved
07/17/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
07/17/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide heating and cooling load calculations to justify the heating/cooling capacities of the two specified mini-split systems. Reference: Section C403.1.1 and C502.2.3, IECC 2018.
2. The minimum slope for a condensate drain is 1%, not 0.02% as stated in note 6 on sheet P-HUB1. Reference: Section 307.2.1, IMC 2018.
3. Provide an inline check valve in the discharge of the condensate drain pump for each mini-split air handling unit. Reference: Section 307.2.4.1, IMC 2018.
07/17/2020 ROBERT SHERRY WATER REVIEW Completed
07/24/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide complete compliance with the 2018 IECC for the lighting.
07/24/2020 DTRAMME1 ENGINEERING REVIEW Passed
08/07/2020 STEVE SHIELDS ZONING REVIEW Approved
08/20/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheets G1 and G4; Code Data (Design Occupant Load): This section references the IBC Table 1004.1. Please revise that reference for the 2018 IBC.
2. Sheets G1 and G4; Code Data (Minimum Door Width): This section references the IBC Section 1008.1.1. Please revise that reference.
3. Sheets G1 and G4; Code Data (Travel Distance): This section references the IBC Table 1016.1. Please revise that reference.
4. Sheets G1 and G4; Code Data: Please review all code reference sections and tables listed in the Code Data. Revise all references to correspond to the 2018 IBC.
5. Sheets G1 and G4; Code Data (Employee Work Areas): This section references the 2010 ADA Standards. This project is reviewed under the 2009 ICC/ANSI. Please revise.
6. Sheet G4; Symbol Legend: The Tactile Exit Signage note and the Tactile Emergency Exit Signage references a Detail X/A-0.1. Please revise that reference.
7. Sheet A1; Notes By Symbol: Note 7 was not located on the Floor Plan. Please verify.
8. Sheet A1.1; Notes By Symbol: Note 9 was not located on the plan. Please verify.
9. Sheet A2; Reflected Ceiling Plan: Please indicate all exit signs on this plan.
10. Sheet A5; Notes By Symbol: Note 4 was not located on the elevations. Please verify.
11. General: Please provide written responses to all review comments.
08/20/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed