Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM04375
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/13/2020 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 07/17/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 07/17/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide heating and cooling load calculations to justify the heating/cooling capacities of the two specified mini-split systems. Reference: Section C403.1.1 and C502.2.3, IECC 2018. 2. The minimum slope for a condensate drain is 1%, not 0.02% as stated in note 6 on sheet P-HUB1. Reference: Section 307.2.1, IMC 2018. 3. Provide an inline check valve in the discharge of the condensate drain pump for each mini-split air handling unit. Reference: Section 307.2.4.1, IMC 2018. |
| 07/17/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 07/24/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide complete compliance with the 2018 IECC for the lighting. |
| 07/24/2020 | DTRAMME1 | ENGINEERING | REVIEW | Passed | |
| 08/07/2020 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 08/20/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheets G1 and G4; Code Data (Design Occupant Load): This section references the IBC Table 1004.1. Please revise that reference for the 2018 IBC. 2. Sheets G1 and G4; Code Data (Minimum Door Width): This section references the IBC Section 1008.1.1. Please revise that reference. 3. Sheets G1 and G4; Code Data (Travel Distance): This section references the IBC Table 1016.1. Please revise that reference. 4. Sheets G1 and G4; Code Data: Please review all code reference sections and tables listed in the Code Data. Revise all references to correspond to the 2018 IBC. 5. Sheets G1 and G4; Code Data (Employee Work Areas): This section references the 2010 ADA Standards. This project is reviewed under the 2009 ICC/ANSI. Please revise. 6. Sheet G4; Symbol Legend: The Tactile Exit Signage note and the Tactile Emergency Exit Signage references a Detail X/A-0.1. Please revise that reference. 7. Sheet A1; Notes By Symbol: Note 7 was not located on the Floor Plan. Please verify. 8. Sheet A1.1; Notes By Symbol: Note 9 was not located on the plan. Please verify. 9. Sheet A2; Reflected Ceiling Plan: Please indicate all exit signs on this plan. 10. Sheet A5; Notes By Symbol: Note 4 was not located on the elevations. Please verify. 11. General: Please provide written responses to all review comments. |
| 08/20/2020 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |