Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T20CM04053
Parcel: 114540620

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM04053
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/06/2020 JPEELDA1 FIRE REVIEW Approved
07/09/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
07/09/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide heating and cooling load calculations to justify the heating/cooling capacities of the two specified mini-split systems. Reference: Section C403.1.1 and C502.2.3, IECC 2018.
2. The minimum slope for a condensate drain is 1%, not 0.02% as stated in note 6 on sheet P-HUB1. Reference: Section 307.2.1, IMC 2018.
3. Provide an inline check valve in the discharge of the condensate drain pump for each new and relocated mini-split air handling unit. Reference: Section 307.2.4.1, IMC 2018.
07/09/2020 ROBERT SHERRY WATER REVIEW Completed
07/15/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide compliance with the 2018 IECC for the lighting.
2. Provide for Tamper Resistant Receptacles where applicable per NEC 406.12.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code.
07/20/2020 DTRAMME1 ENGINEERING REVIEW Passed
08/03/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/03/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet G1; Drawing Index: The Index does not indicate Sheet AD2.1. Please verify.
2. Sheet G1; Drawing Index: The Index does not indicate Sheet RX4. Please verify.
3. Sheet G4; Floor Plan: Per the IBC Section 1017.3, the exit access travel distance shall be measured along the natural and unobstructed path of horizontal and vertical (not diagonal) egress travel to an exit. Please revise.
4. Sheet AD1.1; Enlarged Plan 2: This plan indicates Notes 17 and 18, which are not included in the 'Notes by Symbol'. Please verify.
5. Sheet AD2; Reflected Ceiling Plan: The 'Notes by Symbol' indicates Notes 1 and 2, which were not located on the plan. Please verify.
6. Sheet A1; Detail 4: This detail is shown twice on this sheet. Please revise.
7. Sheet A1; Legend: The Window Designation, Door Designation, and Finish Designation reference a sheet that is incomplete. Please provide.
8. Sheet A1 (Floor Plan); Sheet HUB1: The Floor Plan indicates an Enlarged Plan 3/HUB1 at the Group Sales Room 113, while Sheet HUB1 indicates this area as 2/HUB1. Please verify.
9. Sheet A1 (Floor Plan); Sheet HUB2: The Floor Plan references an Enlarged Plan 3/HUB2 at the Group Sales Room 113. Please revise that reference.
10. Sheet A1 (Floor Plan); Sheet HUB1: The Floor Plan references an Enlarged Plan 2/HUB1 at the Consulting Room 112. Please revise that reference.
11. Sheet A1 (Floor Plan); Sheet HUB2: The Floor Plan references an Enlarged Plan 2/HUB2 at the Consulting Room 112. Please revise that reference.
12. Sheet A1; Floor Plan: The Pharmacy Room 110 has no enlarged plan references on this sheet. Please provide.
13. Sheet A2; Reflected Ceiling Plan: Please verify all enlarged plan references on this sheet are correct.
14. Sheet A3; New Plan Notes: Notes 10 and 12 reference details on Sheet A4.1. Please revise that reference.
15. General: Please provide written responses to all review comments.
08/20/2020 STEVE SHIELDS ZONING REVIEW Approved