Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T20CM04050
Parcel: 140420120

Address:
7073 S PLUMER AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM04050
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/22/2021 STANTEC 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T20CM04050 REV2
NEW FUELING FACILITY (DEFERED SUBMITTAL - PARKING CANOPY)

GENERAL:
To facilitate a shorter back-check time, we request that you please, only provide plans and calculation pages that have been revised, clouding any changes, along with a written response to each of the noted items indicating the action taken.

ARCHITECTURAL REVIEW COMMENTS:
Denied

Parking Canopy Drawings
1. The deferred submittal drawings provided have not been reviewed by the architect or engineer of record as required by 2018 IBC Sec. 107.3.4 and 107.3.4.1. Further, the drawings for this parking canopy do not match the information provided on Sheet S-005. Sheet S-005 presents 4 column lines whereas Sheet S2 of 3 presents 3 column lines. Will the columns align with the parking layout? {The parking canopy on Sheet S-005 does scale 100 feet long which matches Sheet S2 of 3.}

Calculations
1. On Page D1 change the reference to the City of Tucson (currently references the City of Chandler). {Recommend changing to the sentence to read “…local jurisdiction amendments.” to avoid this issue in the future.}

Final Status

Task End Date Reviewer's Name Type of Review Description
10/25/2021 DBENOIT1 APPROVAL SHELF Completed
10/25/2021 DBENOIT1 OUT TO CUSTOMER Completed
10/25/2021 DBENOIT1 REJECT SHELF Completed