Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 2ND
Permit Number - T20CM04050
Review Name: REVISION - - 2ND
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/14/2021 | STANTEC | 2ND PARTY REVIEW | REVIEW | Reqs Change | ARCHITECTURAL COMMENTS Parking Canopy Drawings 1. The deferred submittal drawings provided have not been reviewed by the architect or engineer of record as required by 2018 IBC Sec. 107.3.4 and 107.3.4.1. Further, the drawings for this parking canopy do not match the information provided on Sheet S-005. Sheet S-005 presents 4 column lines whereas Sheet S2 of 3 presents 3 column lines. Will the columns align with the parking layout? {The parking canopy on Sheet S-005 does scale 100 feet long which matches Sheet S2 of 3.} Calculations 1. On Page D1 change the reference to the City of Tucson (currently references the City of handler). {Recommend changing to the sentence to read “…local jurisdiction amendments.” to avoid this issue in the future.} |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/14/2021 | JGARCIA1 | APPROVAL SHELF | Completed |
| 10/14/2021 | JGARCIA1 | OUT TO CUSTOMER | Completed |
| 10/14/2021 | JGARCIA1 | REJECT SHELF | Completed |