Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM03992
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/02/2020 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 07/06/2020 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Passed | |
| 07/07/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | If the shower does not have a listed, pre-fabricated receptor (e.g. a concrete shower base), provide details to show that the construction of the shower floor complies with the requirements of Section 421.5, IPC 2018. |
| 07/07/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. There are two outside air calculations in sheet M1: clarify which one is correct. Reference: Section 107.2.1, IBC 2018. 2. Provide heating and cooling load calculations to justify the heating/cooling capacity of DAC-1 in a room that is also served by HP-1. Reference: Section C403.1.1 and C502.2.3, IECC 2018. |
| 07/07/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 07/14/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 07/29/2020 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 07/29/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A3; Floor Plan: A section cut at the restrooms references 1/A6. Please revise that reference. 2. Sheets A3 and A5; Floor Plans: Please indicate the shower seat, handshower, and grab bar locations on these plans per the ICC/ANSI Section 608. 3. Sheets A3 and A5; Floor Plans: The showers must have the 36"x48" clear floor space to meet the accessibility requirements indicated in the ICC/ANSI Figure 608.2.1. Please verify. 4. Sheets A3 and A5; Floor Plans: The restroom doors must open out of the stall and be located across from the water closet as indicated in the ICC/ANSI Figure 604.9.2. Please verify. 5. Sheet A3; Floor Plan: Please indicate the location of the required service sink. 6. Sheet A4; Ceiling Plan: Please indicate the exit signs on this plan. 7. Sheet A5; Enlarged Restroom Plan: A section cut at the restroom is not complete. Please provide. 8. Sheet A6; Interior Partition Sections 4 and 5: The partition studs indicate 2x6 and 2x3 5/8". For metal studs, omit the 2x portion of the call out. 9. General: Please provide written responses to all review comments. |
| 08/17/2020 | STEVE SHIELDS | ZONING | REVIEW | Approved |